Insulation Resistance Test of Transformer

แชร์
ฝัง
  • เผยแพร่เมื่อ 25 ธ.ค. 2024

ความคิดเห็น • 48

  • @humanbeing4097
    @humanbeing4097 9 หลายเดือนก่อน +2

    Superb detailed videos,that every videos should have.

  • @nkvaishnav6395
    @nkvaishnav6395 3 ปีที่แล้ว +4

    Nice Explanation point to point...Will wait for next video.. Quality video..

  • @akhtarhussainshah7435
    @akhtarhussainshah7435 2 ปีที่แล้ว +4

    It is the ratio of reading taking after 15 or 30 seconds to reading taking after 60 seconds with same coonection as your video. Both readings are taken in one step. The purpose of this test is to ensure integrity of the winding insulation.

  • @shashanksahu2326
    @shashanksahu2326 2 ปีที่แล้ว +4

    It is really a very helpful video. It has cleared all my doubts. Thank u sir.

  • @earnmoney2505
    @earnmoney2505 2 ปีที่แล้ว +2

    Thank you sir🙂 ,this is very helpful .

  • @erwinreyes5888
    @erwinreyes5888 5 หลายเดือนก่อน +1

    thank you so much for your helpful videos

  • @erisherm.8451
    @erisherm.8451 2 ปีที่แล้ว +2

    Very informative indeed 👍

  • @jaydoctor7824
    @jaydoctor7824 2 ปีที่แล้ว +2

    Thank you sir for your educational video.

    • @theengineeringpower4213
      @theengineeringpower4213  2 ปีที่แล้ว

      You are welcome. Keep in touch for more educational videos related to practical Electrical Engineering.

  • @benjaminotettey6315
    @benjaminotettey6315 ปีที่แล้ว +1

    I love the explanation

  • @judebarnes7595
    @judebarnes7595 3 ปีที่แล้ว +4

    Nice work - thank you for posting this video. In the calculations you compensate based on room temperature. Should you instead be compensating for transformer oil temperature.

    • @theengineeringpower4213
      @theengineeringpower4213  3 ปีที่แล้ว +1

      You are right. In this video, for simplification ambient temperature is used. However for accurate calculation, the transformer oil temperature must be used, Thanks for your valuable comment.

  • @kiwidevo1
    @kiwidevo1 3 ปีที่แล้ว +5

    What voltage are you setting the megger to for each test H-XG X-HG and HX-G ?

    • @theengineeringpower4213
      @theengineeringpower4213  3 ปีที่แล้ว +2

      For a High voltage i.e. 220kV or 500kV transformer, the megger testing set rating must be 5 kV. For medium voltage i.e. 11kV, megger set of 1kV rating is OK.

  • @chandanjana6964
    @chandanjana6964 ปีที่แล้ว

    Informative, Thnx sir.

  • @smartengineeringeee4990
    @smartengineeringeee4990 11 หลายเดือนก่อน

    Please give the reference informations in detail that where did you get it.

  • @esauogutu1702
    @esauogutu1702 4 วันที่ผ่านมา

    What is the need of shorting the hv yet it is delta ?

  • @dengakairup
    @dengakairup 3 หลายเดือนก่อน +1

    You are right 👍

  • @goodman12310
    @goodman12310 4 หลายเดือนก่อน

    is the 20 ' c the temperature of winding of the ambient temperature ,
    another thing would this work with dry transformers ?
    thanks

  • @Kishore_.035
    @Kishore_.035 2 ปีที่แล้ว +1

    What is the resistance value at a temperature of 40 degree celcius

  • @rangerrojo5047
    @rangerrojo5047 3 ปีที่แล้ว +2

    Nice work. What books do you suggest about this topic?

    • @theengineeringpower4213
      @theengineeringpower4213  3 ปีที่แล้ว +1

      Thanks. As someone practically associated with sub-stations and T/Lines, I would suggest to study updated articles from the internet as the testing sets are evolving with time.

  • @ziaullhaqzahid3458
    @ziaullhaqzahid3458 หลายเดือนก่อน +1

    Helpful

  • @cedarelectric7763
    @cedarelectric7763 5 หลายเดือนก่อน

    How dovi test for the temperature of the transformer oil

  • @JhonTesfahun
    @JhonTesfahun 2 ปีที่แล้ว +1

    nice work.

  • @cedarelectric7763
    @cedarelectric7763 5 หลายเดือนก่อน

    How do we adjust the temperature of the oil of the transformer

  • @kdmq
    @kdmq ปีที่แล้ว +1

    It's OK to say that any transformer is safe to operate at 20 Celsius, but what if the manufacturing company knows that the transformer is going to be subjected to ambient temperatures much hotter than 20 Celsius? Isn't it better to apply the IR test for the maximum operating temperature. For example, if the transformer is being used in hot summer climates where the temperature regularly reaches 35 Celsius, shouldn't we apply the test for 35 Celsius to make sure there will be no arcing at all times of the year?

  • @TwoFaced2
    @TwoFaced2 ปีที่แล้ว +1

    Can you please make videos on testing of power cables

  • @natural6086
    @natural6086 2 ปีที่แล้ว +1

    why did not you use guard terminal.

    • @theengineeringpower4213
      @theengineeringpower4213  2 ปีที่แล้ว +1

      It's used practically in most cases. Not shown here to avoid any confusion for new learners. Guard terminal is a way to minimize the interference from unwanted circuits. So e.g. if we are measuring insulation resistance between primary and ground, we will have to guard the secondary terminal of transformer.

    • @hariharroy
      @hariharroy ปีที่แล้ว

      ​@@theengineeringpower4213Could you please explain in more detail? What do you mean by 'to minimise interference from unwanted circuits'?

  • @86karna
    @86karna ปีที่แล้ว

    How the input supply is injected for testing of transformer?. Input source

    • @theengineeringpower4213
      @theengineeringpower4213  ปีที่แล้ว

      Input source is the megger testing set which has built-in battery (in case of electronic set). While in case of old hand operated manual megger testing set, voltage is produced by rotation of crank.

  • @324amit77
    @324amit77 ปีที่แล้ว

    3:04 isn't it 500kOhm ?

  • @Wolf.88
    @Wolf.88 ปีที่แล้ว +1

    Thanks!

  • @sunildevariya7965
    @sunildevariya7965 2 ปีที่แล้ว +1

    Tnx

  • @akhtarhussainshah7435
    @akhtarhussainshah7435 2 ปีที่แล้ว

    if DAR less the 1 it is dangerous need for maintenance if ration greater then 1 and less then 1.3 the check oil BDV mositure contents and C & DF test of winding if the ratio greater then 1.3 it is good

  • @akhtarhussainshah7435
    @akhtarhussainshah7435 2 ปีที่แล้ว

    Dielectric Absorption Ratio (DAR) Test insulation test ruther then IR test

  • @akhtarhussainshah7435
    @akhtarhussainshah7435 2 ปีที่แล้ว

    DAR b/w HV to LV, LV to G , HV to G

  • @tyd3407
    @tyd3407 2 ปีที่แล้ว +1

    Major Farts 🤣

  • @jasonchristopheraguillon4988
    @jasonchristopheraguillon4988 ปีที่แล้ว

    Insulation Reating of Einding must be not lower Than 10Giga ohms not in mega

    • @theengineeringpower4213
      @theengineeringpower4213  ปีที่แล้ว

      As per insulation resistance minimum requirements for a transformer, for each kV atleast we must have 2 Mega Ohm resistance. so based on this, you can calculate minimum insulation resistance requirements for any rating transformer. that will turn out to be in Mega ohms in most cases

    • @esauogutu1702
      @esauogutu1702 ปีที่แล้ว

      ​@@theengineeringpower4213for each KVA or KV?