How to adjust the Transient Delay of your Affordable Diesel Generator

แชร์
ฝัง
  • เผยแพร่เมื่อ 7 ต.ค. 2024
  • This video instructs you how to adjust the Transient Delay of your Affordable Diesel Generator. This may be necessary in the event that your generator is shutting down due to over/under frequency or over/under voltage alarm because of the startup of a large load such as air conditioning units, compressors, or large refrigeration units.
    For more information visit www.AffordableGenerator.com

ความคิดเห็น • 75

  • @ridamuftah2500
    @ridamuftah2500 2 ปีที่แล้ว +2

    This video very useful for me, I used this function with heavy staring current load, thanks alot Engineer

  • @prime91st99
    @prime91st99 9 ปีที่แล้ว +1

    Thanks for this man give me more knowledge about dse panel..affordable diesel thanks a lot

  • @jmwaku1865
    @jmwaku1865 4 ปีที่แล้ว

    The video helps me to find a solution of over voltage... Thank you !

    • @damarihenrik7285
      @damarihenrik7285 3 ปีที่แล้ว

      You all prolly dont give a shit but does someone know of a tool to get back into an Instagram account?
      I was stupid lost my password. I appreciate any help you can give me.

    • @theodoredarian7889
      @theodoredarian7889 3 ปีที่แล้ว

      @Damari Henrik instablaster :)

    • @damarihenrik7285
      @damarihenrik7285 3 ปีที่แล้ว

      @Theodore Darian i really appreciate your reply. I found the site thru google and Im in the hacking process now.
      Looks like it's gonna take a while so I will get back to you later when my account password hopefully is recovered.

    • @damarihenrik7285
      @damarihenrik7285 3 ปีที่แล้ว

      @Theodore Darian it worked and I actually got access to my account again. I'm so happy:D
      Thank you so much you saved my ass !

    • @theodoredarian7889
      @theodoredarian7889 3 ปีที่แล้ว

      @Damari Henrik happy to help :D

  • @dldchannel1316
    @dldchannel1316 5 หลายเดือนก่อน

    Already did but why the setting keeps coming back to its original after switching off the key switch. Thanks for your reply

  • @duncanvogel6991
    @duncanvogel6991 2 หลายเดือนก่อน

    Hi Mark just wanna find out how to set fuel priming and engine cool down time on the controller

  • @heartofthetraitorAMINE
    @heartofthetraitorAMINE 3 ปีที่แล้ว

    Thanks

  • @mdrana-kp3kt
    @mdrana-kp3kt ปีที่แล้ว

    Nice

  • @TheAnd1982
    @TheAnd1982 4 ปีที่แล้ว +2

    Hi sir.. please give me some advice about my generator. It always automatically shut down and it says "generator locked out".

  • @AdnanJayyousi
    @AdnanJayyousi 8 หลายเดือนก่อน

    I have a case where there is a chiller connected using star-delta and the GenSet trips, do you think it will help ?

  • @kelebogilemeje4138
    @kelebogilemeje4138 2 ปีที่แล้ว +1

    Why do you suggest max of 0.7 ,what if it is set at 2.2, what would happen to the generators?

  • @zelekeayalewbaychekn4260
    @zelekeayalewbaychekn4260 2 ปีที่แล้ว +1

    hello hello my dear i have 100kva perkiness generator
    when i tray to start after starting
    the generator stops
    and
    on the display
    over frequency
    how can i adjest it

  • @sundayalaiya9602
    @sundayalaiya9602 3 ปีที่แล้ว +1

    Hi, if my generator does not have ignition key to switch on before I proceed to transit delay, is it possible for me to still carry out the transit delay?

  • @philipaddae3628
    @philipaddae3628 4 หลายเดือนก่อน

    My generator is over frequency what should I do

  • @Tanha_8817
    @Tanha_8817 5 หลายเดือนก่อน

    How to reduce or increase the running meter of the generator

  • @lalitarora1522
    @lalitarora1522 3 ปีที่แล้ว

    How to resolve negative phase sequence problem and dg not stop during on this condition.

  • @atkingapu7040
    @atkingapu7040 11 หลายเดือนก่อน

    how to fix under and over voltages in cumins control DSE 8610 KII

  • @DorahQuaicoe
    @DorahQuaicoe 6 หลายเดือนก่อน

    Dg generator shutdown when I put new AVR on it what causes that

  • @mohamedsiyam7447
    @mohamedsiyam7447 5 ปีที่แล้ว +2

    Sir!
    How to update generator controller
    Please answer to me

  • @ГригорГригор-у1й
    @ГригорГригор-у1й 10 หลายเดือนก่อน

    Hello. how to turn on the ignition without starting the engine ? DSE 7320

  • @aliahmedaltrhone2066
    @aliahmedaltrhone2066 2 ปีที่แล้ว

    So what's the ECU warning ⚠️? please

  • @553castrojhay
    @553castrojhay ปีที่แล้ว

    Hi sir my deepsea controller is DSE7310 volvo penta engine 500kva if I start up my generator 10 to 20 second monitor showing ecu amber .and generator under voltage.please give me advise

  • @abdullahhamadeh
    @abdullahhamadeh 2 ปีที่แล้ว

    Hello, i have a problem with my kubota generator, when the generator shuts down ,it will not cut the power, it makes the electricity feather or turns on and off while shutting down, i need help on how to fix that

  • @ameirrashid2285
    @ameirrashid2285 3 ปีที่แล้ว +2

    What is couse of generator under frequency?

  • @quyetho3417
    @quyetho3417 4 ปีที่แล้ว

    Instruction to install smartgen screens?

  • @spiritualviking8094
    @spiritualviking8094 2 หลายเดือนก่อน

    Trying to find out how to remove the low water level alarm but im failing. Any help? The water level is okay and everything runs as it should but the alarm wont go away

  • @ahmadrasooli7666
    @ahmadrasooli7666 4 ปีที่แล้ว

    Hi, bro, I have two generators with using ATI automatic transfer switch system my DG,s are running will but when 12 hours of one DG is completed it gives the signal the other DG set get a start but the previous one does not get stops what is the reason when I bring down the main circuit breaker of DG after some time The DG which will be turned off will get off

  • @jimeejeason1576
    @jimeejeason1576 3 ปีที่แล้ว +1

    Dear sir
    how to reset under frequency shutdown power please explane me because my power generator auto shoutdown and in desplay soing under frequency shoutdowna

    • @ismailali7318
      @ismailali7318 3 ปีที่แล้ว

      I have this problem under frequency so why did you solve it

  • @DieselGeneratortraining
    @DieselGeneratortraining ปีที่แล้ว

    Thanks #powerlearningchannel

  • @mansooraziz1236
    @mansooraziz1236 2 ปีที่แล้ว

    How increase display light

  • @calluula
    @calluula 5 ปีที่แล้ว +1

    I have probelm my generator started and few second off massage ECM and picture engine

  • @edgarboleche9457
    @edgarboleche9457 4 ปีที่แล้ว +1

    Sir I have problem with my generator 750kva it start but after a seconds it will off and and the monitor displayed voltage cannot be reached,sir what is the main reason in that problem.

    • @charlieangkor8649
      @charlieangkor8649 4 ปีที่แล้ว

      the main reason is that the generator is overly complicated.

  • @asgharafridi3300
    @asgharafridi3300 3 ปีที่แล้ว

    Sir here one problem generator
    Alarm
    Gun Under frequency
    Shutdown

  • @jimmyayohan8019
    @jimmyayohan8019 4 ปีที่แล้ว

    Sir what is problem my genset cummins 4bt3.9-g2 the engine high running acceleration is rough and shaking after 1 minute ,and don't start in automatic but he start in manual starting

  • @aliaziz7842
    @aliaziz7842 3 ปีที่แล้ว

    What reason appear code (stoping) on screen generating 7320

  • @omolarafaith8504
    @omolarafaith8504 4 ปีที่แล้ว

    Please what can cause crank down on deep sea 4510 version

  • @wildeagle3736
    @wildeagle3736 2 ปีที่แล้ว

    If you set up this genset,no more password?

  • @monicamoreno9354
    @monicamoreno9354 4 ปีที่แล้ว

    Hello because it throws me a memory corruption message after resetting the module when doing the service and it does not turn on

  • @RajaKumar-bd1tt
    @RajaKumar-bd1tt 3 ปีที่แล้ว

    Perkines generator code spn 110
    Please tell me problem how to sustion

  • @arhamrao5527
    @arhamrao5527 3 ปีที่แล้ว

    When i start diesel engin generator after 3 to 4 days it becomea air lock. Whats problem

  • @muhmmadtariq
    @muhmmadtariq 2 ปีที่แล้ว +1

    Sir Gen over votag gen shtdown

  • @ronneldormido2549
    @ronneldormido2549 4 ปีที่แล้ว

    Hi sir how to fix deep sea electronics 710 the alarm indacte the picture of turtle what is the meaning of these thankyou

  • @rajudakshinamurthy3797
    @rajudakshinamurthy3797 4 ปีที่แล้ว

    I have one dout genratater running but stopped when coming alarm low coolent oil level oil is full on the tank i given flot switch short is ganerater runing

  • @Truthspeaker-c7u
    @Truthspeaker-c7u ปีที่แล้ว

    Can anyone tell me genrator is stoped after 9 secs saying generater at rest how to fix it it says saftey on delay

  • @calluula
    @calluula 3 ปีที่แล้ว

    I have problem my generator shut down and message gen under frequency shud down our generator iveco generator 400 kva

  • @bonifacengunjiri8028
    @bonifacengunjiri8028 3 ปีที่แล้ว

    Hi . I have a generator rated at 110 kva. When I connect it to a 30kw compressor the generator stops running and register under frequency error. What could be the problem?

    • @vinhly4344
      @vinhly4344 2 ปีที่แล้ว

      when i made load testing 110% for my generator 750kVA (pri), it was stop and appear under frequency, cooling water was too hot and blow out at that time,

    • @jamieauriedward9554
      @jamieauriedward9554 ปีที่แล้ว

      It's possible because of the huge added load, which cause the voltage to Dip and in turn causing the Genset to register a lower frequency check and re-adjust your transient delay.
      Or it might be your governor which can't keep up with the load demand

  • @ilkhombakhtiyorov3043
    @ilkhombakhtiyorov3043 11 หลายเดือนก่อน

    I need pin edit DSE 6120

  • @pradhapskr5715
    @pradhapskr5715 3 ปีที่แล้ว

    Can anyone say how can we adjust voltage or rpm in this device through setting

    • @jamieauriedward9554
      @jamieauriedward9554 ปีที่แล้ว

      Voltage, RPM & Frequency are proportional they can be adjusted through the AVR and the engine speed governor

  • @albertboye7057
    @albertboye7057 4 ปีที่แล้ว

    People I wanted to ask if your generator starts alright,but the power did not shoot to where you need to used it,what might be the course?

  • @fendibaene5398
    @fendibaene5398 2 ปีที่แล้ว

    Apa penyakit mensi controller tidak bisa hidup bisa di sentarte Tdk hidup tolong di jelaskan bahasa indonensia

  • @sharifuddin5200
    @sharifuddin5200 4 ปีที่แล้ว +1

    Need bangla tutorial

  • @kienha9791
    @kienha9791 3 ปีที่แล้ว

    CovidImages need to be invested more than half19

  • @orlandopizarro5113
    @orlandopizarro5113 9 ปีที่แล้ว

    i need key edit des7310

  • @charlieangkor8649
    @charlieangkor8649 4 ปีที่แล้ว

    so there are unlabeled symbols for electric transmision pylon, a factory and a sinewave. Which of those means the power grid, the generator and the load? I think the person designing the panel was incompetent and should be fired.

  • @mbkim6215
    @mbkim6215 6 ปีที่แล้ว

    Nice

  • @josephotokunorsackey3895
    @josephotokunorsackey3895 ปีที่แล้ว

    How do one trace earth fault on a generator set

  • @nishad9048
    @nishad9048 2 ปีที่แล้ว

    I connect 30kw 3 phase motor to 100kw generator but when it ON getting under voltage alarm let me know y

  • @mafioso530
    @mafioso530 6 ปีที่แล้ว +1

    Is there anything else I can do to to get this generator yo start. We did this already and didn't work. The generator doesn't have anything hooked up to it and it says under voltage

    • @TheMemphiscash
      @TheMemphiscash 5 ปีที่แล้ว

      Saul sanchez check your voltage regulator

    • @mitchimal
      @mitchimal 5 ปีที่แล้ว

      If t's a large load motor, use a VFD on the motor so initial load is much lower

  • @محمداسيل-ض5ت
    @محمداسيل-ض5ت 2 ปีที่แล้ว

    At my DSE 6110 running time always 0 h 0 m please help