Check Compressor Windings With The Insulation Tester - Fluke 1507

แชร์
ฝัง
  • เผยแพร่เมื่อ 17 ม.ค. 2025

ความคิดเห็น • 39

  • @ahmedsawni862
    @ahmedsawni862 4 หลายเดือนก่อน

    Thank you so much for sharing the knowledge 👍

  • @rodericktirol3799
    @rodericktirol3799 2 ปีที่แล้ว +2

    Great, you explain it in a simple way to understand,i gain knowledge to it, never mind the feeling genius comment,good job.

    • @jollyscaria1922
      @jollyscaria1922 ปีที่แล้ว

      Shering very good welcome allgues best fulcomecome careful serching and jobd anyway outdide es good sllthd time

  • @jasonfoster9118
    @jasonfoster9118 ปีที่แล้ว +4

    I'd like to make a correction. Anything less than 1 Megaohm is considered a failure, while in reality, I've seen motors run with less than that. 50 Megaohms is a very good reading.

  • @hamidab1639
    @hamidab1639 ปีที่แล้ว +1

    Thanks for easy explanstion

  • @Electric-Air-Service
    @Electric-Air-Service ปีที่แล้ว

    Very good video..

  • @chrissipple1018
    @chrissipple1018 ปีที่แล้ว +2

    I'm glad that someone has enough knowledge to not use a Supco merger on a Copeland Scroll compressor. People need to read Copelands ligature about megging their scroll compressors. I'm sure there have been many of the Copeland scroll compressors that were still good but were replaced by using the Supco meggers.

    • @hvacwilly6037
      @hvacwilly6037 ปีที่แล้ว

      I have the Supco Megger. I don’t trust that thing. Isn’t it only good for like small fan motors/ small reach in compressors ?

    • @chrissipple1018
      @chrissipple1018 ปีที่แล้ว +1

      @@hvacwilly6037 Supco Meggers are ok for what you said, for reciprocating compressors but for scroll's I would not use them. For some reason they have made them that they will not read low enough. I've condemned a couple Copeland compressors when the Supco merger said that it was bad, until I read the Copeland literature on their scroll compressors. What I use is a cheap $45.00 Chinese merger I got off of Amazon. They are as accurate as a Fluke merger, just don't trust the voltage readings. I've been using one for about 8 years and it has been accurate so far.

  • @Tirumalaaircontrols
    @Tirumalaaircontrols 2 ปีที่แล้ว +1

    What is acceptable value insulation resistance minimum in compressor

  •  2 ปีที่แล้ว +8

    You should measure insulation with double voltage of operational voltage.

    • @deddie4645
      @deddie4645 6 หลายเดือนก่อน

      So there's a single phase 220 compressor I should be testing at 500 V.

    •  6 หลายเดือนก่อน +2

      @@deddie4645 Exactly

    • @xraybravo7180
      @xraybravo7180 4 หลายเดือนก่อน

      Says who ?

    •  4 หลายเดือนก่อน

      @@xraybravo7180 Proffesion

  • @bills6946
    @bills6946 5 หลายเดือนก่อน +1

    It is not a 2 phase compressor. It is a single phase compressor at 240 volts. Both hot legs are center tapped in the distribution transformer as a delta configuration to create the neutral for 240 volts, hot to neutral is 120 volts. If it were derived from a wye configuration, it would be 120/208 volts the common from both legs is the neutral

    • @KINGPAFA
      @KINGPAFA 5 หลายเดือนก่อน

      ??? It is a 3 phase 575 v Scroll compressor!

    • @stargazer7644
      @stargazer7644 6 วันที่ผ่านมา

      He said it was a 3 phase compressor.

  • @hvacrefrigeration5204
    @hvacrefrigeration5204 ปีที่แล้ว +1

    I have always tested motor windings via ohm it out, either by terminal to terminal or terminal to ground.
    3 ph motors should be equal ohms reading if normal, or tested via terminal to ground.
    Single phase motors.
    Ohm out between terminal to terminal first.
    Good windings should like example: R to S =9 ohms
    R to C = 3 ohms and S to C = 6 ohms mean normal.
    Also do the same with 3 phase by terminal ground. If shorted to ground the ohm meter will read something.

    • @globalheatingcooling
      @globalheatingcooling  ปีที่แล้ว +5

      Insulation tester tests winding insulation by applying DC voltage through the winding & Multimeter measures the resistance of winding. Insulation tester gives an accurate and fast measurement to verify the condition of insulation.

    • @markm0000
      @markm0000 ปีที่แล้ว +1

      There's 2 seperate ways to check a motor. Using a normal multimeter that only outputs a few volts and a mega ohm meter that can output 1000v. The higher voltage will check if the insulation is cracked anywhere and leaking power to ground. It can detect shorts through bad refrigerant full of acids inside the compressor.

  • @Tirumalaaircontrols
    @Tirumalaaircontrols 2 ปีที่แล้ว

    Is this compressor what is acceptable resistance value good and bad

  • @ld7103
    @ld7103 2 ปีที่แล้ว

    Great 👍

  • @ld7103
    @ld7103 2 ปีที่แล้ว +1

    Would u test between N & L on a motor or just phases? And phases & Earth

    • @AquaTech225
      @AquaTech225 2 หลายเดือนก่อน

      Good question I’m not sure. But would like to know the answer also

    • @stargazer7644
      @stargazer7644 6 วันที่ผ่านมา

      You can't test between N&L because there's load there, not an open. A megger tests how good an OPEN is.

  • @cowoganteng3776
    @cowoganteng3776 ปีที่แล้ว

    👍👍👍🙏🙏🙏🙏🙏

  • @josepholuwasheyifunmi8782
    @josepholuwasheyifunmi8782 ปีที่แล้ว

    Please, can i do the same test with Fluke 115 multimeter?

    • @KINGPAFA
      @KINGPAFA ปีที่แล้ว +1

      No, with a multimeter, you could only test to see if the compressor is grounded or not! An insulation tester will test the condition of the insulation on windings, whether it is good or bad or on its way out!

  • @mikeadler434
    @mikeadler434 ปีที่แล้ว

    👍👍

  • @deddie4645
    @deddie4645 6 หลายเดือนก่อน

    Would one of you you 2 people at least give the same information you tested the same voltage or test it at double the voltage ratedV

  • @chhuangaralte2078
    @chhuangaralte2078 ปีที่แล้ว

    Who wa t to swap Fluke 87 V MAX with Fluke 1507

  • @SupremeRuleroftheWorld
    @SupremeRuleroftheWorld 11 หลายเดือนก่อน

    so, technically a third of that compressor is still good. put it back in and send it!

  • @fieldpiecenorthgreece
    @fieldpiecenorthgreece 2 ปีที่แล้ว +2

    Bro!!! That was a bad as video!!! Keep going!!!

  • @joehead1294
    @joehead1294 2 ปีที่แล้ว

    Don't think your getting on the conductors good. The holes where the screws go in are not the conductors, it's the metal tabs around them. Also Copeland doesn't recommend to meg ohm their scroll compressors. Something about the windings being too close to the shell.

    • @globalheatingcooling
      @globalheatingcooling  2 ปีที่แล้ว +1

      I had a very good connection and the holes that where screws go in are conductors as well! An insulation tester measures the resistance of the windings! There is no such thing that you can't use an insulation tester on Copeland Scroll Compressors!