NEC Motor Load Calculations Example

แชร์
ฝัง
  • เผยแพร่เมื่อ 29 ธ.ค. 2024

ความคิดเห็น • 78

  • @Sincoola27
    @Sincoola27 ปีที่แล้ว +12

    I took this guys full prep class a few years ago. Passed my masters exam on the first try thanks to it! great teacher

  • @soundman2604
    @soundman2604 2 ปีที่แล้ว +5

    Very well laid ou,t with Code articles as references. Nice job!

    • @electrical1019
      @electrical1019  2 ปีที่แล้ว

      Thank you!

    • @jeremyjpegan
      @jeremyjpegan ปีที่แล้ว +1

      agreed! Thank you for the schooling. Do you do anything on motor controls?

    • @electrical1019
      @electrical1019  ปีที่แล้ว

      Thank you, it's what our goal is! We're hoping to have some material on controls as well as basic branch wiring up once the fall semester of school is out!

  • @TheMadhatter0710
    @TheMadhatter0710 ปีที่แล้ว +1

    Information is thrown out very thoroughly. Thumbs up!

  • @daltondelaney9534
    @daltondelaney9534 ปีที่แล้ว +3

    Why do you always use 75C degrees column for motor feeder wire size? (8:30 in video)

    • @JV503
      @JV503 9 หลายเดือนก่อน +3

      110.14 NEC

  • @stevenwarren206
    @stevenwarren206 ปีที่แล้ว +10

    The overloads are calculated at nameplate FLA, right? Everything else is calculated from the FLC from from 430 tables , am I right about this?

    • @electrical1019
      @electrical1019  ปีที่แล้ว +1

      For field calculations that is correct. These lectures are intended for students taking a licensing exam in Kentucky, in which on the exam typically the FLC is used to calculate overload protection.

    • @santiagocid5908
      @santiagocid5908 ปีที่แล้ว +1

      You are right 👍

    • @reynaldomartinez4918
      @reynaldomartinez4918 6 หลายเดือนก่อน

      I find that pretty odd since the motor nameplate FLA is tipically different than the FLC. If the FLC is much higher than the FLA by many amps, then the overload will be set much higher than the FLA.. interesting

    • @wesleythorpe7855
      @wesleythorpe7855 3 หลายเดือนก่อน

      @@electrical1019wouldn’t you use the FLA from the name plate for overload for exam purposes as well? It calls out name plate in the code reference.

  • @JesusCruz-wt2zp
    @JesusCruz-wt2zp ปีที่แล้ว +2

    Your videos are great. Please do more ..

    • @electrical1019
      @electrical1019  ปีที่แล้ว

      Thank you! We are always looking to upload new content!

  • @controlsgirl
    @controlsgirl ปีที่แล้ว +1

    Great example!! Way to walk through it!

  • @EbagOmocaigid
    @EbagOmocaigid ปีที่แล้ว +3

    wouldn't the feeder size in step 5 be calculated as THWN-2 like the motor wires? And thus be a number 6 wire rated for 75 AMPS? Great video though, thanks

  • @Luminous116
    @Luminous116 6 หลายเดือนก่อน +2

    I've noticed you use 75° column for the branch ckt conductor size. However I was told to use 60°C column for circuits rated 100 amperes or less (per NEC 110.14-C) regardless of conductor insulation rating. Was there an exception that I missed?

    • @Makitafan
      @Makitafan 5 หลายเดือนก่อน

      I'm not sitting in front of my code book but he said all motors are size it 75 degree column. Finger your way through 430 and see if you can find something backing up his statement.

    • @mywifesboyfriendisfire
      @mywifesboyfriendisfire 2 หลายเดือนก่อน

      He used 90°C for the branch circuits since we're told we're running THWN-2 wire to the motors. The *feeders* to the panel main breaker are calculated using the 75°C column for motors.

  • @kylecropanese8744
    @kylecropanese8744 10 หลายเดือนก่อน +1

    Thank you so much about to go for my exam shitting bricks this helps so much

    • @marmars1081
      @marmars1081 9 หลายเดือนก่อน

      Did you pass?

  • @wadetaney8642
    @wadetaney8642 ปีที่แล้ว

    Well put!! Great teacher.

  • @rigobertoruiz6136
    @rigobertoruiz6136 หลายเดือนก่อน

    Amazing video thanks!

  • @MrTomObama
    @MrTomObama หลายเดือนก่อน

    On step #3 if its THWN-2 at 9.5 amps wouldn't the answer be 18 for copper? Or is it 14 because of the temp rating? Confused. I understand how you got the answer for the 65 amps just not the 9.5 amps.

  • @mcarroll598
    @mcarroll598 ปีที่แล้ว +1

    When you size breakers for motors, wouldn’t you round down to the next standard circuit breaker size?

    • @electrical1019
      @electrical1019  ปีที่แล้ว +3

      430.52 exception number 1 allows us to go up to the next standard size for overprotective devices serving branch circuits for motors; 430.62 does not have this exception, so we have to go down to the next standard size for overcurrent devices serving feeder circuits for motors.

    • @mcarroll598
      @mcarroll598 ปีที่แล้ว +1

      @@electrical1019 thank you so much

  • @MensLifestyle1985
    @MensLifestyle1985 11 หลายเดือนก่อน

    For Step #6, why wouldn't you add 150A to 20A for the remaining motor? Why did you only add the FLC and not the Branch Circuit protection from step #4 like you did for the larger motor?

  • @BobbaFett312
    @BobbaFett312 ปีที่แล้ว +1

    i have same question as others on using 75C when ampacity column. 75C can be used only when terminations are also 75C. why is 75C used here?

  • @hebrewlessons2348
    @hebrewlessons2348 2 หลายเดือนก่อน

    great great great instruction!

  • @juliorojas7276
    @juliorojas7276 5 หลายเดือนก่อน +1

    Service factor is 1.4 and the code is 1.5 or grater to be × 125%. If is not 1.5 por greater it should be × 1.15.

  • @CallmeDr773
    @CallmeDr773 7 หลายเดือนก่อน

    Super helpful! Thank you

  • @oscar27ization
    @oscar27ization ปีที่แล้ว +10

    I think you made a small mistake by multiplying your overload protection device with your FULL LOAD CURRENT instead of your FULL LOAD AMP??

    • @sekwanmerritt6235
      @sekwanmerritt6235 ปีที่แล้ว +1

      Yes for step 3 Sizing the Branch Circuit conductor he multiplied a %125 by the value of Overload Protection instead of the instead of the Full Load Current.

    • @paulpbe1
      @paulpbe1 3 หลายเดือนก่อน +1

      Overload size should be sized by the amperage on the motor name plate not the the FLC table

  • @mcarroll598
    @mcarroll598 ปีที่แล้ว +1

    Wouldn’t you size your OVERLOADS to your FLA on the motor? Not your FLC from the code book?

    • @electrical1019
      @electrical1019  ปีที่แล้ว +1

      In the field/"real-world", yes, you would. This video assumes you do not have that information, and is more for those taking a licensing exam rather than practical application.

    • @mcarroll598
      @mcarroll598 ปีที่แล้ว +1

      @@electrical1019 thanks. One other question. I understand how to size for fuses and breakers but what’s confusing is when you round up or round down. Any explanation would be great. Thank you.

    • @electrical1019
      @electrical1019  ปีที่แล้ว +1

      @@mcarroll598 I believe we just responded to that in another comment you left!

    • @mcarroll598
      @mcarroll598 ปีที่แล้ว +1

      @@electrical1019 thank you

  • @narendergodara1992
    @narendergodara1992 ปีที่แล้ว

    EXCELLENT VEDIO👌👌🙏🙏

  • @Mike-ec4zp
    @Mike-ec4zp ปีที่แล้ว +1

    Where does table 430.22(E) fall in these steps? If asked for any of these rating percentages? Answer be helpful

    • @electrical1019
      @electrical1019  ปีที่แล้ว

      You would only use table 430.22(E) if you are sizing conductors for a motor that is not continuous duty (step 4). The NEC tells us that anytime we use a motor we have to consider it to be for continuous duty unless we meet certain conditions, so we generally speaking don't bring this table up. If you are using this information for real work application, and you consistently work with intermittent use motors like on an elevator, it is very good to know though!

  • @thanmaysudev
    @thanmaysudev 7 หลายเดือนก่อน

    Could you please tell me why the 40hp motor doesn't have any starter

  • @mr.write1433
    @mr.write1433 ปีที่แล้ว

    what nec edition is this ?

  • @Tito-nw6te
    @Tito-nw6te ปีที่แล้ว

    How can i get these work sheets ??

  • @Primez8902
    @Primez8902 ปีที่แล้ว +1

    You dont need the FLA to do these calculations?

    • @Primez8902
      @Primez8902 ปีที่แล้ว +1

      Im using the 2014 code book

    • @electrical1019
      @electrical1019  ปีที่แล้ว +1

      Actually, FLA comes from the motor nameplate. FLC comes from tables 430.248 and 430.250. 430.6(A)(1) requires us to use the FLC from the tables for all calculation other than overload protection rather than the FLA (in this videos we assume that the FLA is not provided and just use the FLC for over overload protection). Hope that helps!

  • @kythuatcongnghiep8559
    @kythuatcongnghiep8559 ปีที่แล้ว

    thank you, very helpfully for me

  • @paasdfasd
    @paasdfasd 3 หลายเดือนก่อน

    what happens if the motor is 400V AC?

  • @purpleraptor1183
    @purpleraptor1183 ปีที่แล้ว

    I am doing 50 HP [FLC= 65A, 65A*125% = 81.25A got Conductor size AWG 4] and 250 HP [FLC= 302A, 302A*125% = 377.5A got Conductor size AWG 500MCM table 310.16(75 ,Copper)]. For 50 HP - I am doing 65 A * 250% = 162.5 Amp breaker. But from ugly book, for 50 HP size breaker-150A. Same for 250 HP - 302 * 250% = 755 A. Should I not go up and standard size of breaker?

    • @johnnyroloff8118
      @johnnyroloff8118 10 หลายเดือนก่อน

      I think it is because the 250% from Table 430.52(C)(1) is a maximum rating, so the ugly book selects the closest standard size under 250% of the FLC.

  • @mr.write1433
    @mr.write1433 4 หลายเดือนก่อน

    FLA not equal to flc? Why put FLC?

  • @scottdonahue6417
    @scottdonahue6417 4 หลายเดือนก่อน

    There is a standard 70 amp breaker by the way

  • @Kowloonhongkong
    @Kowloonhongkong 11 หลายเดือนก่อน

    why dont protect the wire?

  • @stuffthings9618
    @stuffthings9618 ปีที่แล้ว

    Arent you supposed to calculate the Overload from nameplate amps????

    • @Resistculturaldecline
      @Resistculturaldecline ปีที่แล้ว

      If the nameplate info is provided, you are to use nameplate for separate overload devices. If nameplate is not given, you're to use table FLC. At least, that how I think I understand it.

  • @aaronwidder9624
    @aaronwidder9624 ปีที่แล้ว +2

    I thought if you rated your ocp at 250% it would be the next "lowest" size breaker or if it's sized at 125% it would be the next "highest" size breaker? Great Info sir! 👍

    • @aaronwidder9624
      @aaronwidder9624 ปีที่แล้ว

      @@mitcheljames7053 ooo ok, I read over that and understand now. Thanks for the clarification sir! 🫡

    • @theonetrueanthonylong1843
      @theonetrueanthonylong1843 ปีที่แล้ว

      @@mitcheljames7053 Yes, thank you!

    • @electrical1019
      @electrical1019  ปีที่แล้ว

      It looks like we got beat to the explanation, but yes, Mitchel provided a perfect breakdown of why we are able to go up to the next size breaker!

  • @natename797
    @natename797 ปีที่แล้ว

    Why is the first wire size not # 18?

    • @TheMoody2006
      @TheMoody2006 ปีที่แล้ว

      I'm looking for the same answer. I THINK he made a mistake with the chart (read the AMPS as the wire size) but was technically correct because 14 AWG is the smallest size permissible for a branch circuit.

  • @kentbinaoro9164
    @kentbinaoro9164 ปีที่แล้ว

    I am now very confused, but anyways I only know things for residential wiring only, I thought 14awg must use 15a breaker to protect the wire

    • @Makitafan
      @Makitafan 5 หลายเดือนก่อน

      The "test" gave a wire insulation choice that was in the 90 degree C column. So that's why it was chosen.

  • @cevtongooden1836
    @cevtongooden1836 ปีที่แล้ว

    Thanks so much send more

  • @danielgriffin2674
    @danielgriffin2674 ปีที่แล้ว

    Some guys are just cut out to be teachers, nice job.

  • @TheKaracay
    @TheKaracay 3 หลายเดือนก่อน

    he messed up on overload for big motor other than that I like the way he teaches

  • @alexramos9459
    @alexramos9459 11 หลายเดือนก่อน

    So I just did this by calculator and field knowledge on wires and experience wiring things actual amperage it’s 7.7 not 6 learning ohms law helps a lot and makes easy to calculate by using the calculator

  • @pingpongpaddlehead
    @pingpongpaddlehead 8 หลายเดือนก่อน

    fascinating

  • @jass1989
    @jass1989 ปีที่แล้ว +1

    Last i checked. 1.4 was less than 1.5
    Mis heard him

    • @jacobhess3n327
      @jacobhess3n327 5 หลายเดือนก่อน

      Yeah I’m confused too. There are inaccuracies throughout the entire video

    • @jass1989
      @jass1989 5 หลายเดือนก่อน

      ​@jacobhess3n327 I re-watched it. Sf of the motor is 1.4. Code says 1.15 or greater. 1.4 is .35 great then 1.15.

  • @orangaharris640
    @orangaharris640 ปีที่แล้ว +1

    Beginer here.. dont understand most of it 😅