HMI MITSUBISHI GS-2107-WTBD CONNECT PLC OMRON NX1P2 9024DT

แชร์
ฝัง
  • เผยแพร่เมื่อ 11 ก.ย. 2024
  • HELLO EVERYONE. TODAY I WILL CREATE PROJECT:
    CONNECT PLC OMRON NX1P2(9024DT) - HMI MITSUBISHI GS-2107 (MODBUS TCP/IP)
    + CONFIG PLC OMRON NX1P2-9024DT: MODBUS TCP/IP - modbus client (USE FUNCTION MODBUS TCP SERVER )
    - CREATE PROJECT SOFTWARE SYSMAC STUDIO
    - SETTING IP 192.168.0.123.
    - ADD LIBRARY OEN_Communication_V1_0_22(1.0.22,Omron Electronics Norway AS)
    +++ Modbus TCP_SERVER (OEN\Modbus)
    - Create varible give funtion block (port,mobus_coil,input_res,Holding_register,...)
    - adjust varible mod_access_list (choise type Write,Read,Read\Write)
    - Create function block MOBBUS_SERVER( IP connect =192.168.0.1 port 502)
    - create functions to read data and write data value communication Modbus TCP (holdding register)
    - complie program and upload program PLC
    - Online and create: Watch(Project)1 or Watch(Table)1 - Program0.HOLDING_REGISTER
    + CONFIG HMI MITSUBISHI GS-2107 :(CONFFIG MODBUS MASTER)
    - CREATE PROJECTS SOFTWARE GT_DESIGNED 3
    - SETTING CHOICE MODBUS MASTER CONNECT ETHERNET IP (MULTI)
    - SETTING IP HMI :192.168.0.1 , SETTING MODBUS SLAVE : SATTION 1 ( IP:192.168.0.123) PORT 502
    - CREATE 2 BUTTON CONTROL WRITE HOLDING REGITER 0 ( BIT 0: ON, BIT 1:OFF)
    - CREATE LAMP READ HOLDING REGISTER 1 (BIT 0 1:ON ,O OFF)
    - CREATE NUMBERIC INPUT: WRITE HOLDING REGISTER 2 GET IN PLC OMRON
    - CREATE NUMBERIC DISPLAY: READ HOLDING REGISTER 3 FROM DATA PLC OMRON
    - COMPLIE AND DOWNLOAD PROGRAM GET IN HMI MITSUBISHI GS-2107
    * THANK YOU EVERYBODY WATCHING *