Zurn Wilkins Automatic Control Valves - How it Works

แชร์
ฝัง
  • เผยแพร่เมื่อ 14 ต.ค. 2024
  • This animation shows the internal adjustments made by the Zurn Wilkins ZW209 Automatic Control Valve during normal operation, allowing the valve to hold constant outlet pressure regardless of changing flow rates and inlet pressure. Click here to see more information about the ZW209: www.zurn.com/Pa...

ความคิดเห็น •

  • @mirandagroboske548
    @mirandagroboske548 9 ปีที่แล้ว +3

    Excellent video! Thank you for sharing!

  • @WyrmholeWarrior
    @WyrmholeWarrior 2 ปีที่แล้ว +1

    Easy to understand! Thanks!

  • @paulfox521
    @paulfox521 4 ปีที่แล้ว +1

    That was awesome video

  • @dannychristianto7691
    @dannychristianto7691 7 ปีที่แล้ว +1

    hi.. What would happen if the pressure upsteam the control valve drops below the set point (55 psig)? will it fully open or close? really appriciate your answer... thx

    • @ZurnIndustries
      @ZurnIndustries  7 ปีที่แล้ว

      Hi, Danny. Should the inlet pressure drop below the set point, the valve will be in an open condition, and out of control. The valve requires a minimum of a 10 psi differential across the valve to remain in control.
      If you have any more questions, feel free to contact the Zurn Wilkins Customer Care department at 1-855-ONE-ZURN (1-855-663-9876).

  • @kremesti
    @kremesti ปีที่แล้ว +1

    Are the gauges important for commissioning?

  • @welltime4645
    @welltime4645 หลายเดือนก่อน

    There no crd what happened?

  • @smsom1591984
    @smsom1591984 6 ปีที่แล้ว

    Hi , what is the difference between this type and the type with Low-flow Bypass ? Thanks

    • @ZurnIndustries
      @ZurnIndustries  6 ปีที่แล้ว

      All ACVs of the Pressure Reducing variety have minimum
      continuous flow requirements. As long as the minimum continuous flow rate
      is above the minimum flow rate of the ACV, no low-flow by-pass is needed.
      In the event the flow rate drops below the minimum continuous flow rate of the
      ACV, a low-flow by-pass is called for. In the case of the ZW209BP, we add
      a small direct acting Pressure Reducing Valve to the backside of the ACV.
      The small PRV will handle all low-flows through 10 GPM. This is the main
      difference between the ZW209 and the ZW209BP.

    • @smsom1591984
      @smsom1591984 6 ปีที่แล้ว

      thank you for reply . one more thing , in case of no flow , will downstream pressure stay at set pressure by using the ZW209 or need to add Bypassin this case ?

  • @TanweerAhmed
    @TanweerAhmed 5 ปีที่แล้ว

    Good explained about PRV