4 Concrete Test Live Practical | Slump Test | Cube test | Temperature Test | Rebound hammer Test

แชร์
ฝัง
  • เผยแพร่เมื่อ 21 ธ.ค. 2024

ความคิดเห็น •

  • @chandrashekhar3929
    @chandrashekhar3929 2 ปีที่แล้ว +15

    Explained very nicely.
    Slump test is done to test water cement ratio which has direct impact on the design strength of concrete. The reduction in height after the cone is removed depends on the type of concrete vis a vis design strength. For example concrete of M20, M25, M30 etc have different reductions in height after the cone is removed.

  • @QualityEngineer819
    @QualityEngineer819 3 ปีที่แล้ว +4

    Very nice sir prectical video dekh kr bhut kuch sekhne ko mila
    Again Thank you so much🙏

  • @shakirraza3255
    @shakirraza3255 3 ปีที่แล้ว +9

    Tremendous job you are doing sir .... Keep it sir

  • @AmoghC
    @AmoghC 3 ปีที่แล้ว +14

    For slump test, number of layers is 3 and for each layer the tamping should be 25 times. Care should be taken that while tamping 2nd layer it must not penetrate 1st layer and same for 3rd layer, this test should be completed within 2 min, Ref: IS 1199(part-2):2018 (but your video is informative, keeping growing good luck)

    • @chandramohanpai2082
      @chandramohanpai2082 3 ปีที่แล้ว +4

      Test taken to make a video l don't think in india any bulider will waste time in such tests concrete comes pour it work done go home that is regular practise time pass video

    • @muqeemkhan8860
      @muqeemkhan8860 3 ปีที่แล้ว +1

      Now the standard has been change. You must penetrate the previous layer by 1 inch. The way he test the slump is bulshit. Slump must be fill in 3 layer. 1st layer 7 cm. 2nd layer 16 cm. 3rd layer 30 cm. Tamping in each layer must be 25 time.

    • @rashidhussain6182
      @rashidhussain6182 ปีที่แล้ว +1

      I agree with you

  • @Whistleblowerz
    @Whistleblowerz ปีที่แล้ว +2

    Amazing video sir, most knowledgeable I can guarantee. Thank you so much. Keep providing us such valuable content. Thank you sir.

  • @ayushjain4249
    @ayushjain4249 3 ปีที่แล้ว +18

    As per IS code 1199 2018.......We fill the slump cone in 3 layer of 25 time stroke each...The hole procedure should be done within the 3 min time frame

    • @princetomar6363
      @princetomar6363 3 ปีที่แล้ว

      Right

    • @atoullshukkla5625
      @atoullshukkla5625 3 ปีที่แล้ว

      I also noticed same he said 4 layer 25-28 tamping Totally wrong.
      And again said 35 tamping in cube filling, he doesn't know any thing

    • @princetomar6363
      @princetomar6363 3 ปีที่แล้ว

      @@atoullshukkla5625 25 time is right

    • @princetomar6363
      @princetomar6363 3 ปีที่แล้ว

      I can proof

  • @sagarprakashkudekar6852
    @sagarprakashkudekar6852 3 ปีที่แล้ว +30

    Apka jo KN/Nmm2 ka volume ata hai usko grade of concrete se divided karo usse pata chalega ki kitna % hai

    • @sanjaykamble8537
      @sanjaykamble8537 2 ปีที่แล้ว

      ........

    • @karansahni6843
      @karansahni6843 2 ปีที่แล้ว

      adhoora gyan nhi please, KN/mm² ka volume? ye kya cheez hoti hai yrrr

    • @karansahni6843
      @karansahni6843 2 ปีที่แล้ว

      value likho typing error mtt kro boht freshers isi me confuse ho jayenge

  • @errishavsingh3767
    @errishavsingh3767 2 ปีที่แล้ว +3

    At 21:32 jo 22.5 hai wo metre me hona chahiye kyuki 150mm*150mm=22500mm ata hai aur isko metre me convert karne pe ye 22.5metre ho jata hai.....aur 600kilo N hai ya only Newtown? Bhai mujhe kuch jagah calculation explaining me error laga hai...

  • @krunalbrahmbhatt6775
    @krunalbrahmbhatt6775 3 ปีที่แล้ว +5

    Thank you brothet for giving practical information👍🏻🤝🏻🙂

  • @halalmeatshophk
    @halalmeatshophk 3 ปีที่แล้ว +86

    did you made a mistake in the estimate of 28days strength? you wrote 30 * 28 / 100 , whereas it should be 30 * 99 / 100, am i right ?

    • @yogeshgoyal5133
      @yogeshgoyal5133 3 ปีที่แล้ว +4

      Correct bole, Yhi me bolne vala tha

    • @simpledaud2778
      @simpledaud2778 3 ปีที่แล้ว +1

      22.5 kaise liya sir ne?

    • @princetomar6363
      @princetomar6363 3 ปีที่แล้ว

      th-cam.com/video/sJ7bp_fAW74/w-d-xo.html

    • @paporidas4642
      @paporidas4642 3 ปีที่แล้ว +2

      please clear this doubt civil site visit. i have this doubt too.

    • @bobbleheadxtreme3801
      @bobbleheadxtreme3801 3 ปีที่แล้ว +5

      Strength = load/ area of mould
      = load/22.5

  • @vijaybhojane8460
    @vijaybhojane8460 2 ปีที่แล้ว

    MASS Scientific Sales Mr. Mahipat is very good work

  • @abhinavgupta6199
    @abhinavgupta6199 2 ปีที่แล้ว +2

    Cement ke grade par bhi nirbhar karta hai na sir

  • @girishkumarpradhanpradhan7919
    @girishkumarpradhanpradhan7919 3 ปีที่แล้ว

    best valuable civil engg site technical knowledge

  • @bikashsahoo999
    @bikashsahoo999 3 ปีที่แล้ว +1

    Jaldi se jaldi 1 million hoga

  • @matukanpandey5310
    @matukanpandey5310 2 ปีที่แล้ว +3

    1 sample pe 3 specimen ready kiya jaata h na..???

  • @tangshukraireang6789
    @tangshukraireang6789 3 ปีที่แล้ว +8

    how did you get area of cube as 22.5 ? if you divide 600 with 22.5 how comes your strength of concrete in kn/mm2. please rectify your mistakes bro.

  • @IndianHeart07
    @IndianHeart07 2 ปีที่แล้ว +5

    22:25 Actually 7 days me 67% strength and 14 days days मे 87% strength achieved होनी चाहिए according with IS code 🙏

  • @microflyer2020
    @microflyer2020 ปีที่แล้ว +1

    sir mere yaha Thekedar n mistri k sath mil k dhokha de diya...... double shift m kam kara rh th night 8 Baje ka bana masala jo ki pilar casting m use hona th usko next day 11 am k aas pas extra cement mila kar Pilar casting kr diya...... y masala 2 pilar m use kiya gy th 4 ya 5 feet ka pilar cast kiya th... jo ki plinth beam k niche use hua th... plinth beam Ground level s 7 feet upar h jisme soil filling ki gyi h.... aaj building 3 floor ki h... ky hm log safe h???? area 1200sq mtr 14 column h jo ki 9*12 size k h.. 4 tmt bar 16mm k & 2 bar 12 mm k h in each column.. plinth n niche brick work only outer beam k niche kiya gy all four side baki andar soil filling h only... plz help

  • @ertauseef2
    @ertauseef2 3 ปีที่แล้ว

    Bhut hi badia video h Sir G.👍

  • @BQCCB23
    @BQCCB23 3 ปีที่แล้ว +1

    Practical dekh kar confidence bad gya sir

  • @amaze-o-tronics4576
    @amaze-o-tronics4576 2 ปีที่แล้ว +1

    Very nicely carried out practical concrete various tests and explained to understand even dull student. Best video

  • @AmitThakur-nk8zz
    @AmitThakur-nk8zz 3 ปีที่แล้ว +1

    Very nice u r sharing greatful knowledge

  • @hansrajparmar9500
    @hansrajparmar9500 3 ปีที่แล้ว +2

    Vah sir
    Love you from devbhumi dwarka ❤

  • @msrajput7096
    @msrajput7096 3 ปีที่แล้ว +1

    Sir agr humne 10 M3 ka concrete site pe mngaya h to jo gddi usko leke ayegi hume kaise pta chlega k usme purra 10m3 maal aya h plz tell?

  • @natvarsinhzala3122
    @natvarsinhzala3122 3 ปีที่แล้ว

    Thankyu so much sir ji👏👌👌Mene to apke ye test ke video pahle dekhe the aek aek krke lekin aaj fir se revision ho gaya sirjii superb plz sir or video banao jisse hame pura knowledge mil ske 🥰🥰👌👌👌🌷🌷🌷

    • @devrajsinghmarwadi4679
      @devrajsinghmarwadi4679 3 ปีที่แล้ว

      1 sariya Fitter+ 1 helper = _____ Kg.
      1 Carpenter+ 1 Helper= ______ sqm.
      8 ghante Ki Job me.
      Kitna Productivity Hota he practically.

  • @SurajKumar-oc3he
    @SurajKumar-oc3he 3 ปีที่แล้ว

    Sir bahot maaza aa raha h aap ka video dekh kr k

  • @dm9636615039
    @dm9636615039 2 ปีที่แล้ว +1

    Sir 0 to 5 m3 quantity ka mtlb kya hai. Ek bar jo concrete ban rha hai vo ya din bhar me jo bn rha hai vo ya total work me concrete bnega vo

    • @asgarali3046
      @asgarali3046 2 ปีที่แล้ว

      Bhai RMC m 7 m^3 se jyada concrete nhi aata so jitna quantity v RMC m aata h site p usi ko measure Krna hota h or uska report v banana padta h

  • @officialerdharmendrapatel5118
    @officialerdharmendrapatel5118 3 ปีที่แล้ว

    Compaction test krana hain soil ka ho jayega kya ji

  • @MohitYadav-dl4ik
    @MohitYadav-dl4ik 3 ปีที่แล้ว +1

    Sir please batiya roof may bend ayga Gaya bataiye abhi Kya

  • @anilkumarsharma8901
    @anilkumarsharma8901 3 ปีที่แล้ว

    Engineering👨‍🔧 key bahut video🎥 hain 😇😇😇
    Apni bhasha ki baat hee kuch aur hain😇😇😇😇😇

  • @xlr8killerr704
    @xlr8killerr704 3 ปีที่แล้ว

    🙏 aapka bohot aabhar🙏🙏🙏

  • @asifnakwa135
    @asifnakwa135 3 ปีที่แล้ว +3

    ASTM standard as per 3 layer not 4 layer flings slump cone also lifting slump cone within 5-+2 second asper ASTM

    • @logiclessmind1525
      @logiclessmind1525 3 ปีที่แล้ว

      Cube should be filled in 3 layers and slump cone should be filled in 4 layers

    • @shaikhfayaz8696
      @shaikhfayaz8696 2 ปีที่แล้ว

      @@logiclessmind1525 please let me know standard?

  • @gulubabu2237
    @gulubabu2237 3 ปีที่แล้ว +1

    Lafarge concerto acha hai kya 🤔

  • @the_real_adarsh9082
    @the_real_adarsh9082 3 ปีที่แล้ว +1

    jittaa 4 saal me nhi pdhaaa uttnnaa 40 min me btaadiyaa sir aapne or site construction vaale ques. laauyee sir ap 🤗🤗🤗🤗

  • @syedmohtashimali7434
    @syedmohtashimali7434 3 ปีที่แล้ว +1

    Hello Assalamualaikum good to see this video love it ...

  • @ranapratapdatta370
    @ranapratapdatta370 3 ปีที่แล้ว +3

    Pillars are already constructed upto base level.but sudden shortage of money had kept the construction work on suspension for five months. Do u think it will damage the bar that are open from the pillars

    • @chandrashekhar3929
      @chandrashekhar3929 2 ปีที่แล้ว +1

      Cement wash the exposed rebars including stirrups to prevent formation of rust. Rust is very dangerous as there won't be proper bondage with the concrete if the rebars have become rusty.

    • @rameshangala3565
      @rameshangala3565 2 ปีที่แล้ว

      Chemical coat for rods will be added advantage

  • @manmagicman8149
    @manmagicman8149 2 ปีที่แล้ว +2

    hi bro. i have contruction plan for 10000 sqft slab G+1. do we really required Soil Report ? pls advice

  • @thedesiboys647
    @thedesiboys647 ปีที่แล้ว +5

    7 din ke liye apne 65 se multiply karbaya or 28 din ke liye direct 28 se ye kya baat Hui engineer sahab

  • @ankit4625
    @ankit4625 3 ปีที่แล้ว +1

    Great effort sir... 🙏🙏

  • @renushailsunnass6808
    @renushailsunnass6808 2 ปีที่แล้ว +2

    The slump test is considered failed as per bs when the concrete collapse. The concrete is too watery.
    Desired values are between 40 and 80 unless it's a pump mix with extra cement.
    The method for raising the cone is inappropriate, he should lift the cone from a higher or standing position.
    Anyway good initiative to show test on site. Kudos

  • @thesunil920
    @thesunil920 4 หลายเดือนก่อน

    Very helpful video sir..❤

  • @Journey-Moment
    @Journey-Moment 3 ปีที่แล้ว +2

    Which type of rod should be used for tamping in case of slump test?

  • @parvejalam7284
    @parvejalam7284 3 ปีที่แล้ว +3

    Very helpful Video for freshers sir thanks for making this.....these three test are very very important for civil engineer bring some more videos 👍

  • @SantoshSingh-fj8fs
    @SantoshSingh-fj8fs 2 ปีที่แล้ว

    Sir..agar column remound hammer testing me fail ho jaate hain too uske baad ky kare... hardness badane ke ky tarike honge

  • @ShakirUllah-c9i
    @ShakirUllah-c9i 4 หลายเดือนก่อน

    Sir slump leyar is three or four??

  • @SagarKumar-kp3fc
    @SagarKumar-kp3fc ปีที่แล้ว

    1 sample = 3 cube IS 456.....
    30×28/100 wahh bhai Quality Engineer

  • @ravishnirman
    @ravishnirman 2 ปีที่แล้ว +1

    As per BSEN or ASTM for the slump testbitz only 3 layers...BSEN its says equal hight of layers,ASTM its says equal quantity for layers

  • @tausifmta786
    @tausifmta786 2 ปีที่แล้ว

    Thnkuu for giving knowledge concrete testing

  • @ganeshprasad8740
    @ganeshprasad8740 3 ปีที่แล้ว +1

    Sir my building column are crack steel have rusted now' how we repair this ? Only repair plaster or other guide me

    • @scorpionjj5079
      @scorpionjj5079 3 ปีที่แล้ว

      Society manager se baat karo 😀

    • @mo_rojgar
      @mo_rojgar 3 ปีที่แล้ว

      Sabse pehele app wo concrete nikal kai apply anti rusting liquid after that apply some binding liquid and fill with micro concrete lastly plaster the surface for finishing
      App pehele chk karlo kaha sai seepages hai ki nahi usko band kijiye

    • @ganeshprasad8740
      @ganeshprasad8740 3 ปีที่แล้ว

      @@mo_rojgar I am repairs the columns with steel jacket nd fill concrete thanks for reply too late

  • @Itscricket25
    @Itscricket25 ปีที่แล้ว

    Agar temperature jiada hoyega 35 degree se..to keya problem hoyega concrete ma.

  • @SantoshSingh-fj8fs
    @SantoshSingh-fj8fs 2 ปีที่แล้ว

    Sir failure hone pr ...baad me uska solutions kaise kare ..uss pr bhi video banaye🙏🙏

  • @MAURYAffFASTCLIPS-cj5dz
    @MAURYAffFASTCLIPS-cj5dz 3 ปีที่แล้ว +1

    Sir ....plz provide us details of companies who r providing a internship in ludhiana. ....

    • @nagarajup1392
      @nagarajup1392 3 ปีที่แล้ว

      Plz this is not procedure for filling the slump cone should be filled with scoop

  • @abushahma7787
    @abushahma7787 ปีที่แล้ว

    amazing video...very interesting

  • @heartless4394
    @heartless4394 2 ปีที่แล้ว

    Sir, thermometer ka concrete inserting time k liye kya refrence code h ???

  • @entertainmentchannel8952
    @entertainmentchannel8952 3 ปีที่แล้ว

    Please, please Slab ke vibration ke bareme datail me video banaye, slab ke size ke according standard vibration kitna hona chahiye oh commen people vibromeeter application se kaise count kare yeh bataye, mera 10x12 ka living room hai usme vibrometer se ek standard football ko 6ft hight se chhodne se 2.5 mm tak ka vibration show karta hai (6ft se chhodne se, na ke patakne se ) toh kya yeh sahi hai?flat new hai

  • @balvindersingh6346
    @balvindersingh6346 3 ปีที่แล้ว +2

    Very helpfull question

  • @YOUR.TRADER
    @YOUR.TRADER หลายเดือนก่อน

    Good TEACHER ❤🎉🎉❤🎉❤

  • @shashwatmishracivilenginee1933
    @shashwatmishracivilenginee1933 3 ปีที่แล้ว

    Ok plz may you share design mix of m30

  • @shaktisehgal9777
    @shaktisehgal9777 2 ปีที่แล้ว

    Sir after how many days should we check rebound hammer test after pillar casting ?

  • @Neerajsahu2045
    @Neerajsahu2045 2 ปีที่แล้ว

    kha hai aapka center

  • @aspirantcivilengineers
    @aspirantcivilengineers 3 ปีที่แล้ว

    Nice Explain & very informative video 👌

  • @anuraggaur5793
    @anuraggaur5793 2 ปีที่แล้ว

    Road Estimator Software pe video bana dijiye plzz plzzz☹☹☹

  • @sanky6898
    @sanky6898 3 ปีที่แล้ว +1

    Water ratio jyada hone par concurit kharab ho jata h??

  • @ajeetaher1490
    @ajeetaher1490 3 ปีที่แล้ว +1

    as per new amendment slump cone test also done in 3 layes

  • @rahulkisku1677
    @rahulkisku1677 3 ปีที่แล้ว

    Sir slump test me kya check krthe hae

  • @raviartist8457
    @raviartist8457 2 ปีที่แล้ว +1

    30*28/100 ya 30*99/100 sir? 22:44

  • @sajidali-indian
    @sajidali-indian 3 ปีที่แล้ว

    Kisi rcc ki qb me pemais kese kare jese colam 15*9*10ft

  • @pritiranjanjena8985
    @pritiranjanjena8985 3 ปีที่แล้ว +3

    Sir sirf cone ka hight 300mm he aap jab check karteho tab app handel se kartho, handels se surface ka hight 300 nehi he jyada he

  • @divisionagent6274
    @divisionagent6274 2 ปีที่แล้ว

    What is that for langue indish ???

  • @engineeringsolutions3516
    @engineeringsolutions3516 3 ปีที่แล้ว +3

    Thanks for this amazing content,

    • @civilpower610
      @civilpower610 3 ปีที่แล้ว

      th-cam.com/video/isWVxNUfpiU/w-d-xo.html

  • @miteshsingh8819
    @miteshsingh8819 2 ปีที่แล้ว

    IS 1199 2018 part-2 me 3 Layer me hi bharna hai ye rivise ho gaya hai

  • @faizan_e_syedzabeebshahsah2858
    @faizan_e_syedzabeebshahsah2858 3 ปีที่แล้ว

    Thanks For The Awesome Content Appreciate From Pakistan

  • @Rajeshbandre7310
    @Rajeshbandre7310 3 ปีที่แล้ว

    Most useful video 👍

  • @reader5933
    @reader5933 2 ปีที่แล้ว

    Very good job sir

  • @SaifAli-ve5gb
    @SaifAli-ve5gb 2 ปีที่แล้ว +1

    Informative

  • @naveenagarwal7665
    @naveenagarwal7665 2 ปีที่แล้ว

    bahut achha sir.
    Aap hmare office Aimil Ltd ki digital machine use kijiye achha result milega .

  • @mahima3501
    @mahima3501 2 ปีที่แล้ว

    Sir slump cone me b 3 layer hoti h. 4 layer modified wale me hota h.

  • @mickyjassal6117
    @mickyjassal6117 หลายเดือนก่อน

    Amezing 😮😮

  • @anantmalusare2911
    @anantmalusare2911 3 ปีที่แล้ว

    Wonder full information

  • @prashantsahu5394
    @prashantsahu5394 3 ปีที่แล้ว

    Sir water level kaise krte hai..
    Floor ko up ya down Krna ho..
    And floor slope kaise dete hai..
    Theory video banao sir...
    Plz Plz plz sir

  • @Amitkumar-cu2pk
    @Amitkumar-cu2pk 3 ปีที่แล้ว

    Sir concrete mix design se video banaye plz

  • @narwaladvanture
    @narwaladvanture 2 ปีที่แล้ว

    Bhai 30x28 krange ya 30x99

  • @civilabhiyantaclasses-by-m7010
    @civilabhiyantaclasses-by-m7010 3 ปีที่แล้ว

    Sir plz ek video brick test ka bhi or tiles ka bhi .waiting for positive response

  • @Raushankumar-kw8bo
    @Raushankumar-kw8bo 3 ปีที่แล้ว

    Please upload this type of more videos

  • @Rahbarify
    @Rahbarify 3 ปีที่แล้ว

    Remould hamer test kitna din ke concrete pe karna chahye

  • @avinashmahapure8315
    @avinashmahapure8315 3 ปีที่แล้ว

    Sir ultrasonic ka bhi video

  • @patleinfo5863
    @patleinfo5863 3 ปีที่แล้ว

    Sir apka whatsapp group join nahi hora full ho gaya hai koi other link provide kare

  • @mickeyvideos318
    @mickeyvideos318 3 ปีที่แล้ว

    plan bnaney se phley load kaise nikala jata hi please answer me

  • @imtajali3723
    @imtajali3723 3 ปีที่แล้ว

    So important video ❤️❤️

  • @nbverma235
    @nbverma235 3 ปีที่แล้ว

    Very informative video sir

  • @rajivranjansingh4310
    @rajivranjansingh4310 2 ปีที่แล้ว

    Nice video very helpful

  • @moizsalah4963
    @moizsalah4963 3 ปีที่แล้ว +1

    Imp question whether u can answer it or not
    Till which grade Slump test is carried out??M30/40/50
    Simultaneously u forgot about one test of concrete which the people are unaware of.
    Waiting for your reply...

  • @m.editor799
    @m.editor799 2 ปีที่แล้ว

    Hammer test casting ke kitne din baad karna hai

  • @shashwatmishracivilenginee1933
    @shashwatmishracivilenginee1933 3 ปีที่แล้ว

    Sir cement kitne kg h m30 design me ?

  • @_fan_video_099
    @_fan_video_099 3 ปีที่แล้ว

    Thnks for this type of video sir👍

  • @wifeslowdrawings8074
    @wifeslowdrawings8074 3 ปีที่แล้ว +8

    28 days ka calculation wrong hai 30*99/100

  • @vishvdipmuneshwar3721
    @vishvdipmuneshwar3721 2 ปีที่แล้ว

    Slab old and new slab joint me small crack aa gaya or pani lick ho raha hai ab kya upay hai?

  • @jncivil1390
    @jncivil1390 ปีที่แล้ว

    Test ka consa grate concrete ha
    Or setting time kitna ha

  • @madhavsingh1918
    @madhavsingh1918 3 ปีที่แล้ว

    Best ever vedio

  • @rajshribarmate2780
    @rajshribarmate2780 3 ปีที่แล้ว

    Sir ......area of cube is (side )×side ×side ....and you are taking only (side × side ) and compressive strength check for 28 day ....the calculation is (30×99/100)
    If l m not wrong ....plz correct me ??

    • @Amiyaaaaaaaaaa
      @Amiyaaaaaaaaaa 3 ปีที่แล้ว

      Side ×side× side volume hota hai bhai